SKU: PGIP04A-BOYWG-GKL
Availability: Out of Stock, Usually leaves warehouse in 7-14 weeks
400 A, 3 Phase, 277/480 VAC, Male Cams (brown, orange, yellow, white, green) Phase Rotation, 2 Wire Stop/Start Terminals, Kirk Key Provision, NEMA 3R Weatherproof, aluminum housing
400 Amp, 3 Phase, 277/480 VAC Power Input Panel. UL Listed NEMA Type 3R for outdoor use. Power Input panels provide a safe, convenient and economical way to connect temporary emergency power from portable generators to a building, in conjunction with a transfer switch.
Power Input Panels are generally permanently mounted to the outside of a building. It has to be located so that the associated portable generator is not near any HVAC air intakes for the facility that might draw in the generator exhaust fumes. The portable generator is connected to the Power Input Panel using 4/0 feeder cable with Cam-type Series 16 connectors. The Power Input Panel is permanently connected to a transfer switch (not supplied by Lex) that is used to switch the building electrical supply from domestic power to the portable generator. A transfer switch must be used to switch the building power between the domestic power supply and the generator for safety and to meet NEC requirements.
Shooting in CT, RI or NY? For lighting
& grip visit: www.barndoorlighting.com
Gently used manufacturer lighting &
grip demos for sale at great prices:
Arri, Kino Flo, Lowel
Sign up for exclusive updates and deals!